Operation control function by the indoor unit control
Protection control
Current protection
1) Maximum current limit control for the outdoor unit (by indoor unit control)
When the operation current of the outdoor unit comes close to the limit, request compressor speed is retained in order to keep the
current.
If the current exceeds the threshold set in Menu 9.1.10, request compressor speed is reduced.
2) Maximum current limit control for electric heater or other heat source
This function is available for 3phase connection only.
If the current on L1 or L2 exceeds the limit, heater output is reduced once every 5 seconds until the current drops to the normal level.
If the current on L3 exceeds the limit, compressor speed is reduced by 6rps every 30 seconds until the current drops to the normal
level.
Freeze protection of water heat exchanger
This function can be activated on Menu 9.3.17
(1) In cooling mode
Compressor speed is kept when the low pressure (BP4) reaches 0.75 MPa, and stopped when it reaches 0.65 MPa for 20 seconds.
Operation is automatically restarted when it reaches 0.83 MPa and the supply water temperature becomes 14°C or higher, but it will
permanently stop if the protection is activated for 3 times within an hour.
(2) In defrosting mode
Compressor stops when the low pressure (BP4) reaches threshold value depending on water temperature.
After stopping, the system automatically restarts with heating mode but the period to prohibit defrost is reduced to 15 minutes.
When the above action is repeated for 10 times, the system stops and error code is displayed.
Low condenser out
Compressor stops when the supply temperature (BT12) becomes below 5°C and it automatically restarts when the supply temperature
(BT12) becomes above 14°C.
Operation control function by the indoor unit control

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries HMS140VA1 and is the answer not in the manual?

Mitsubishi Heavy Industries HMS140VA1 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelHMS140VA1
CategoryHeat Pump
LanguageEnglish

Related product manuals