8
-
'13 HM-T-193
Technical data
Specifications
Indoor model
HMA100V1
HMA100V2
HMA100VM1
HMA100V1
HMA100V2
HMA100VM1
HMS140VA1
HMS140VA2
HMS140V1
HMS140V2
Outdoor model FDCW71VNX-A FDCW100VNX-A FDCW140VNX-A
Height mm 750 845 1300
W
idth mm
880
(+88 with valve cover)
970 970
Depth mm 340 370
(+80 with foot rail)
370
(+80 with foot rail)
Weight kg 60 81 105
Color Stucco White
Sound power level*
1
dB(A) 64 64.5 71
Sound power level (silent mode) dB(A) 61 62 68
Sound pressure level*
2
dB(A) 48 50 54
Sound pressure level (silent mode) dB(A) 45 47 51
Airow m3/min 50 73 100
Type of compressor RMT5118MDE2 RMT5126MDE2 RMT5134MDE2
Refrigerant oil liter 0.68 M-MA68 0.9 M-MA68 0.9 M-MA68
Heat exchanger M n & inner grooved tubing
straight n & inner grooved tubing
M n & inner grooved tubing
Ref control EEV
Defrost control Reversing cycle
Fan Propeller fan x 1 Propeller fan x 2
Fan motor W 86 x 1 86 x 1 86 x 2
Shock & vibration absorber Rubber sleeve (for compressor)
Electric heater (crank case) W 20
Electric heater (base) W 100 120 120
Safety equipment
Internal thermostat for fan motor
Abnormal discharge temperature protection
Power and signal line from indoor unit 5 core 2.5mm
2
5 core 2.5mm
2
3 core 6mm
2
+
3 core 1.5mm
2
Refrigerant R410A
Refrigerant volume
(pipe length without additional charge)
kg (m) 2.55 (15) 2.9 (15) 4.0 (15)
Dimensions, refrigerant pipe mm (inch) Gas pipe: OD 15.88 (5/8"), Liquid pipe: OD 9.52 (3/8")
Ref pipe connections Frare
Outdoor Unit
Model HT30 MT300 MT500
Power source 1phase 230V / 3phase 400V 50Hz
Volume liter 30 300 480
Volume hot water coil liter 14 21
Material hot water coil Stainless steel
Tapping capacity
12liter/min liter 320 960
16liter/min liter 230 560
Stand-by heat loss*
3
W 82 103
Immersion heater kW 9kW 4steps
Height mm 360 1880 (+20 - 45mm) 1695 (+20 - 55mm)
Width mm 590 600 760
Depth mm 360 600 876
Weight kg 24 1
10 130
IP grade IP21
Color White
Emergency mode thermostat
35/45
Temperature limiter
98 (-8)
Safety valve bar 2.5
Max pressure, Tank bar 2.5
Max pressure, hot water coil bar 10.0
Water quality, domestic hot water
EU directive no 98/83/EF
Dimensions, climate system pipe mm 28
Dimensions, hot water pipe mm 28
Max water pipe length to indoor unit m 10
Max wiring length to indoor unit m 10
Water pipe connection, climate system ISO 228/1 G1B
Water pipe connection, hot water ISO 228/1 G1B
External heat source connection ISO 7/1 Rc1 ISO 228/1 G1
Tank Unit (for HMS140VA and HMS140V only)
*
1: Test condition for sound power level
Temperature condition: Heating condition 2
*
2: Test condition for sound pressure level
Temperature condition: Heating condition 2
MIC position: 1m away in front of outdoor unit at the height of 1m
*
3: According to EN255-3
Test conditions
Water Temperature Ambient Temperature
Heating
condition 1 45
out / 40
in
7
DB / 6
WB
condition 2 35
out / 30
in
condition 3 35
out / 30
in 2
DB / 1
WB
Cooling
condition 1 7
out / 12
in
35
DB
condition 2 18
out / 23
in
Tapping 40
out / 15
in 7
DB / 6
WB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries HMS140VA1 and is the answer not in the manual?

Mitsubishi Heavy Industries HMS140VA1 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelHMS140VA1
CategoryHeat Pump
LanguageEnglish

Related product manuals