Technical data
Specifications
Indoor model
HMA100V1
HMA100V2
HMA100VM1
HMA100V1
HMA100V2
HMA100VM1
HMS140VA1
HMS140VA2
HMS140V1
HMS140V2
Outdoor model FDCW71VNX-A FDCW100VNX-A FDCW140VNX-A
Height mm 750 845 1300
W
idth mm
880
(+88 with valve cover)
970 970
Depth mm 340 370
(+80 with foot rail)
370
(+80 with foot rail)
Weight kg 60 81 105
Color Stucco White
Sound power level*
1
dB(A) 64 64.5 71
Sound power level (silent mode) dB(A) 61 62 68
Sound pressure level*
2
dB(A) 48 50 54
Sound pressure level (silent mode) dB(A) 45 47 51
Airow m3/min 50 73 100
Type of compressor RMT5118MDE2 RMT5126MDE2 RMT5134MDE2
Refrigerant oil liter 0.68 M-MA68 0.9 M-MA68 0.9 M-MA68
Heat exchanger M n & inner grooved tubing
straight n & inner grooved tubing
M n & inner grooved tubing
Ref control EEV
Defrost control Reversing cycle
Fan Propeller fan x 1 Propeller fan x 2
Fan motor W 86 x 1 86 x 1 86 x 2
Shock & vibration absorber Rubber sleeve (for compressor)
Electric heater (crank case) W 20
Electric heater (base) W 100 120 120
Safety equipment
Internal thermostat for fan motor
Abnormal discharge temperature protection
Power and signal line from indoor unit 5 core 2.5mm
2
5 core 2.5mm
2
3 core 6mm
2
+
3 core 1.5mm
2
Refrigerant R410A
Refrigerant volume
(pipe length without additional charge)
kg (m) 2.55 (15) 2.9 (15) 4.0 (15)
Dimensions, refrigerant pipe mm (inch) Gas pipe: OD 15.88 (5/8"), Liquid pipe: OD 9.52 (3/8")
Ref pipe connections Frare
Outdoor Unit
Model HT30 MT300 MT500
Power source 1phase 230V / 3phase 400V 50Hz
Volume liter 30 300 480
Volume hot water coil liter — 14 21
Material hot water coil — Stainless steel
Tapping capacity
12liter/min liter — 320 960
16liter/min liter — 230 560
Stand-by heat loss*
3
W — 82 103
Immersion heater kW 9kW 4steps
Height mm 360 1880 (+20 - 45mm) 1695 (+20 - 55mm)
Width mm 590 600 760
Depth mm 360 600 876
Weight kg 24 1
10 130
IP grade IP21
Color White
Emergency mode thermostat
℃
35/45
Temperature limiter
℃
98 (-8)
Safety valve bar 2.5
Max pressure, Tank bar 2.5
Max pressure, hot water coil bar — 10.0
Water quality, domestic hot water —
≦
EU directive no 98/83/EF
Dimensions, climate system pipe mm 28
Dimensions, hot water pipe mm — 28
Max water pipe length to indoor unit m 10
Max wiring length to indoor unit m 10
Water pipe connection, climate system ISO 228/1 G1B
Water pipe connection, hot water — ISO 228/1 G1B
External heat source connection — ISO 7/1 Rc1 ISO 228/1 G1
Tank Unit (for HMS140VA and HMS140V only)
*
1: Test condition for sound power level
Temperature condition: Heating condition 2
*
2: Test condition for sound pressure level
Temperature condition: Heating condition 2
MIC position: 1m away in front of outdoor unit at the height of 1m
*
3: According to EN255-3
Test conditions
Water Temperature Ambient Temperature
Heating
condition 1 45
℃
out / 40
℃
in
7
℃
DB / 6
℃
WB
condition 2 35
℃
out / 30
℃
in
condition 3 35
℃
out / 30
℃
in 2
℃
DB / 1
℃
WB
Cooling
condition 1 7
℃
out / 12
℃
in
35
℃
DB
condition 2 18
℃
out / 23
℃
in
Tapping 40
℃
out / 15
℃
in 7
℃
DB / 6
℃
WB