3-4 | ni.com
Chapter 3 Analog Output
Routing AO Sample Clock to an Output Terminal
You can route AO Sample Clock to any output PFI terminal. AO Sample Clock is active high
by default.
AO Sample Clock Timebase Signal
The AO Sample Clock Timebase (ao/SampleClockTimebase) signal is divided down to provide
a source for AO Sample Clock. AO Sample Clock Timebase can be generated from external or
internal sources, and is not available as an output from the controller.
AO Start Trigger Signal
Use the AO Start Trigger (ao/StartTrigger) signal to initiate a waveform generation. If you do
not use triggers, you can begin a generation with a software command. If you are using an
internal sample clock, you can specify a delay from the start trigger to the first sample. For more
information, refer to the NI-DAQmx Help.
Using a Digital Source
To use AO Start Trigger, specify a source and a rising or falling edge. The source can be one of
the following signals:
A pulse initiated by host software
Any PFI terminal
AI Reference Trigger
AI Start Trigger
The source also can be one of several internal signals on the cDAQ controller. Refer to the
Device Routing in MAX topic in the NI-DAQmx Help or the LabVIEW Help for more
information.
You also can specify whether the waveform generation begins on the rising edge or falling edge
of AO Start Trigger.
Using an Analog Source
Some C Series modules can generate a trigger based on an analog signal. In NI-DAQmx, this is
called the Analog Comparison Event, depending on the trigger properties.
When you use an analog trigger source, the waveform generation begins on the first rising or
falling edge of the Analog Comparison Event signal, depending on the trigger properties. The
analog trigger circuit must be configured by a simultaneously running analog input task.
Note Depending on the C Series module capabilities, you may need two modules
to utilize analog triggering.

Table of Contents

Other manuals for National Instruments cDAQ-9133

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments cDAQ-9133 and is the answer not in the manual?

National Instruments cDAQ-9133 Specifications

General IconGeneral
BrandNational Instruments
ModelcDAQ-9133
CategoryController
LanguageEnglish

Related product manuals