English – 21
“Move anyway” function
If some safety device is not working or is faulty, it is possible to control and move the gate anyway in “Hold-to-run” mode. For further details,
please refer to the tearout insert “USER GUIDE” (nal part of the manual).
9
DIAGNOSTICS
Some devices are display messages to identify their status and faults.
9.1 - Control unit signals
The leds on the control unit issue signals to indicate their normal/faulty operation.
Table 13 lists the signals:
Table 13
OK LED Cause Solution
Red and green
leds OFF
Serious Check if the power is on; check fuses have not been tripped: if that is the case, check
the cause of the fault and replace with others of the same value.
Red or green
led ON
Serious
malfunction
Try and switch the control unit off for a few seconds; if the situation does not
change, there is a fault and the electronic board must be replaced.
1 green ash a
second
All OK Normal operation of the control unit.
1 red ash
1 sec. pause
1 red ash
the installation of the devices was
not successful or the conguration
of the 1-2 dip switches was changed
without re-learning the devices
Check the correct connection of the alt and photocell inputs (see gure 7 and
paragraphs 8.1.1 and 8.1.2) or if the conguration of micro switches 1-2 has been
changed, perform the device learning procedure (paragraph 5.2)
2 quick green
ashes
There has been a change
in the input status
This is normal when there is a change in one of the inputs: SbS,
STOP, triggering of photocells or the radio transmitter is used.
2 red ashes
1 sec. pause
2 red ashes
Triggering of a photocell At the beginning of the manoeuvre, one or more photocells are preventing movement:
check to see if there are any obstacles.
During the closing movement it is normal if an obstacle is really present.
4 red ashes
1 sec. pause
4 red ashes
Activation of the STOP input At the start of the manoeuvre or during the movement, the STOP input has been
triggered:
check the cause.
5 red ashes
1 sec. pause
5 red ashes
Internal parameter memorisation
error
Wait at least 30 seconds during which the control unit tries to reset. If the situation
does not change,
it is necessary to delete the memory and carry out the storing procedure again
7 red ashes
1 sec. pause
7 red ashes
- Error in the internal circuits.
- conguration of programming
switches 1 and 2 changed
Disconnect all the power circuits for a few seconds, then try again and send
a command; if the situation does not change there may be a serious fault on the
board or on the motor wiring: check and replace as required.
If the conguration of switches 1 and 2 has been modied, repeat the device learning
procedure or reset the previous conguration
8 red ashes
1 sec. pause
8 red ashes
Command already present. Another command is already present. Remove the command to be able to send
more.
PHOTO led Cause Solution
Off Photocell input activated At the start of the manoeuvre, one or more photocells are preventing movement;
check to see if there are any obstacles, also check the NC connection for faults.
On All OK The photocell is aligned and the movement is permitted
STOP led Cause Solution
Off Activation of the STOP input Check the devices connected to the STOP input
On All OK STOP Input active
SbS led Cause Solution
Off Step-by-step command not present
On Step-by-step command present
FCA led Cause Solution
Off FCA limit switch input triggered
On FCA limit switch input closed
FCC led Cause Solution
Off FCC limit switch input triggered
On FCC limit switch input closed
RADIO led R Cause Solution
Off During normal operation, it shows a radio code that is not in the memory has been received.
On Radio transmitter programming or deletion in progress