An expert who is well trained in safety measures, standards, and specifications should be asked to
perform the installation.
Do not install EtherCA
T network equipment near sources of noise.
If the network must be installed in an area subject to noise, take steps to address the noise, such as
placing equipment in metal cases.
Precautions when Installing Communications Cables
Check the following items on the communications cables that are used in the network.
a) Are there any breaks?
b) Are there any shorts?
c) Are there any connector problems?
When you connect the cable to the communications connectors on devices, firmly insert the commu-
nications cable connector until it locks in place.
Do not lay the communications cables together with high-voltage lines.
Do not lay the communications cable near devices that generate noise.
Do not lay the communications cables in locations subject to high temperatures or high humidity.
Do not lay the communications cables in locations subject to excessive dirt and dust or to oil mist or
other contaminants.
There are limitations on the bending radius of communications cables. Check the specifications of
the communications cable for the bending radius.
4-5-3
Installing EtherCAT Communications Cables
Ethernet communications cables and connectors are used to connect the EtherCAT port of the Motion
Controller
with EtherCA
T slaves.
Use a straight, shielded twisted-pair cable (double shielding with aluminum tape and braiding) of
Ethernet category 5 (100BASE-TX) or higher.
The following products are recommended.
Cable with Connectors
Sizes and Conductor Pairs: AWG 26 × 4 Pairs
Product name
Manufac-
turer
Cable
length
(m)
*1
Model
Contact in-
formation
Cable with Connectors on Both
Ends
(RJ45/RJ45)
Standard RJ45 connector type
OMRON
Corpora-
tion
0.3
XS6W-6LSZH8SS30CM-Y
*2
OMRON Cus-
tomer Service
Center
0.5
XS6W-6LSZH8SS50CM-Y
*2
1
XS6W-6LSZH8SS100CM-Y
*2
10 XS6W-6LSZH8SS1000CM-Y
*2
*1. For the latest list of the Cables, refer to the Industrial Ethernet Connectors Catalog (Cat. No. G019).
*2. The Cables are single-shielded, but the communications and noise characteristics are ensured to satisfy
the standard values.
4 Mounting and Wiring
4-13
CK3E-series Programmable Multi-Axis Controller Users Manual Hardware (I610)
4-5 Laying the EtherCAT Network
4
4-5-3 Installing EtherCAT Communications Cables

Table of Contents

Other manuals for Omron CK3E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CK3E Series and is the answer not in the manual?

Omron CK3E Series Specifications

General IconGeneral
BrandOmron
ModelCK3E Series
CategoryController
LanguageEnglish

Related product manuals