5-4-2
Details of Flags
FlashSizeErr
Register name Sys.FlashSizeErr
Description The user program size exceeds the built-in flash memory capacity.
Range 0 to 1
Details 0: No error
1: The user program size exceeds the built-in flash memory capacity
.
Detection timing When save command is issued
Recovery Re-issue save command.
Effects Save command is invalidated.
Cause and cor-
rection
Cause (Assumed cause)
Correction Prevention
The user program size is
too large.
Reduce the size of the user
program.
Or
, delete the backup file.
None
Precautions/
Remarks
None
BufSizeErr
Register name Sys.BufSizeErr
Description The buffer size set in the user program exceeds the built-in RAM capacity.
Range 0 to 1
Details 0: No error
1: Buf
fer size exceeds the built-in RAM capacity
.
Detection timing When power is turned ON or the Controller is reset.
Recovery Cycle the power supply, or issue reset command ($$$)
Effects The buffer size is changed to the default value.
Cause and cor-
rection
Cause (Assumed cause) Correction Prevention
The buffer size set in the
user program is too large.
Reduce the buffer size. None
Precautions/
Remarks
None
AbortAll
Register name Sys.AbortAll
Description Stop by Abort all input
Range 0 to 1
Details 0: No stop by Abort all input
1: Stopped by Abort all input, or stopped in the past by Abort all input.
Detection timing With
Abort all input
Recovery Cycle the power supply, or issue reset command ($$$)
Effects Operation continues
Cause and cor-
rection
Cause (Assumed cause) Correction Prevention
Abort all was input. None None
Precautions/
Remarks
None
5 Error Processing
5-9
CK3E-series Programmable Multi-Axis Controller User’s Manual Hardware (I610)
5-4 Sys.Status Register
5