NoClocks
Register name Sys.NoClocks
Description Cannot detect a phase clock or a servo clock.
Range 0 to 1
Details 0: No error
1: Cannot detect a phase clock or a servo clock.
Detection timing When power is turned ON or the Controller is reset.
Recovery Cycle the power supply, or issue reset command ($$$)
Effects Cannot enable the motor.
Cause and cor-
rection
Cause (Assumed cause) Correction Prevention
The clock-related register is
overwritten by the user pro-
gram.
If the error no longer occurs
after the re-initialization
command ($$$***) is exe-
cuted, review the user pro-
gram.
None
The Motion Controller
failed.
If the error still persists
even after the above cor-
rective actions have been
taken, replace the
Motion
Controller
.
None
Precautions/
Remarks
None
Default
Register name Sys.Default
Description Initialized to the factory default setting.
Range 0 to 1
Details 0: No error
1: Cases below
• In the factory default state, or initialized to the factory default state by a re-initializa-
tion command ($$$***).
• Configuration changed after save command was issued.
Detection timing When power is turned ON or the Controller is reset.
Recovery Cycle the power supply, or issue reset command ($$$)
Effects Operation continues
Cause and cor-
rection
Cause (Assumed cause) Correction Prevention
Re-initialization command
($$$***) was issued.
None None
ConfigLoadErr occurred. Check the corrective action
for each error
.
None
Precautions/
Remarks
None