Connection sta-
tus
Error cause Corrective action example
Gener-
al Sta-
tus
(hex)
Addi-
tional
Status
(hex)
01 0203 Error code gener-
ated by originator
The connection timed out. Timeout of tag data link communication from
the target occurred. Check the power supply to
and cable wiring of the devices on the path in-
cluding the target and switch. If the cause is a
decrease in performance due to heavy load, re-
view the performance design by increasing the
timeout value, RPI, or etc.
01 0204 Error code gener-
ated by originator
The connection open process
timed out.
The target did not respond. Check the power
supply to and cable wiring of the devices on the
path including the target and switch.
01 0302 Error code gener-
ated by originator
or returned from
target
The total pps of the entire
EtherNet/IP settings is more
than 3,200.
Review the EtherNet/IP settings so that pps
does not exceed the limit.
*1. If the number of connections is more than 32, Tag Data Link T
imeout will occur repeatedly. If the controller log contains
repetitive Tag Data Link Timeout records, check if the number of connections is appropriate.
5 Error Processing
5-15
CK3E-series Programmable Multi-Axis Controller Users Manual Hardware (I610)
5-5 EtherNet/IP Connection Status Codes and Troubleshooting
5

Table of Contents

Other manuals for Omron CK3E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CK3E Series and is the answer not in the manual?

Omron CK3E Series Specifications

General IconGeneral
BrandOmron
ModelCK3E Series
CategoryController
LanguageEnglish

Related product manuals