Available FINS Commands Section 6-5
143
6-5 Available FINS Commands
6-5-1 The List of Available FINS Commands
Type Command
code
Name Function
01 01 MEMORY AREA READ Reads consecutive data from the I/O memory
area.
01 02 MEMORY AREA WRITE Writes consecutive data to the I/O memory area.
01 03 MEMORY AREA FILL Fills the specified range of I/O memory with the
same data.
01 04 MULTIPLE MEMORY AREA
READ
Reads non-consecutive data from the I/O mem-
ory area.
I/O Memory
Area Ac-
cess
01 05 MEMORY AREA TRANSFER Copies and transfers consecutive data from one
part of the I/O memory area to another.
02 01 PARAMETER AREA READ Reads consecutive data from the parameter area.
02 02 PARAMETER AREA WRITE Writes consecutive data to the parameter area.
Parameter
Area Ac-
cess
02 03 PARAMETER AREA FILL Fills the specified range of the parameter area
with the same data.
03 06 PROGRAM AREA READ Reads data from the user program area.
03 07 PROGRAM AREA WRITE Writes data to the user program area.
Program
Area Ac-
cess
03 08 PROGRAM AREA CLEAR Clears the specified range of the user program
area.
04 01 RUN Switches the CPU Unit to RUN, MONITOR, or
DEBUG mode.
Execution
Control
04 02 STOP Switches the CPU Unit to PROGRAM mode.
05 01 CONTROLLER DATA READ Reads CPU Unit information.Configura-
tion Read
05 02 CONNECTION DATA READ Reads the model numbers of the specified Units.
06 01 CONTROLLER STATUS READ Reads the CPU Unit’s status information.Status
Read
06 20 CYCLE TIME READ Reads the average, maximum, and minimum
cycle times.
07 01 CLOCK READ Reads the clock.Clock Ac-
cess
07 02 CLOCK WRITE Sets the clock.
Message
Access
09 20 MESSAGE READ/CLEAR Reads/Clears messages and FAL(S) messages.
0C 01 ACCESS RIGHT ACQUIRE Acquires the access right if no other device holds
it.
0C 02 ACCESS RIGHT FORCED
ACQUIRE
Acquires the access right even if another device
currently holds it.
Access
Right
0C 03 ACCESS RIGHT RELEASE Releases the access right regardless of what
device holds it.
21 01 ERROR CLEAR Clears errors and error messages.
21 02 ERROR LOG READ Reads the error log.
Error Ac-
cess
21 03 ERROR LOG CLEAR Clears the error log pointer to zero.
22 01 FILE NAME READ Reads the file memory’s file information.
22 02 SINGLE FILE READ Reads the specified amount of data from the
specified point in a file.
22 03 SINGLE FILE WRITE Writes the specified amount of data from the
specified point in a file.
22 04 FILE MEMORY FORMAT Formats file memory.
22 05 FILE DELETE Deletes the specified files from file memory.
22 07 FILE COPY Copies a file within file memory or between two
file memory devices in a system.
File
Memory
22 08 FILE NAME CHANGE Changes a file name.
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr

Table of Contents

Other manuals for Omron CS1G-CPU42H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CS1G-CPU42H and is the answer not in the manual?

Omron CS1G-CPU42H Specifications

General IconGeneral
BrandOmron
ModelCS1G-CPU42H
CategoryController
LanguageEnglish

Related product manuals