Cycle Time and Time Section 9-2
195
9-2-3 Differences with CS/CJ Series
Built-in Clock Function The clock of the Ladder Engine is the same as that of the computer when
startup. However, it will not synchronize with the clock of the computer be-
cause it advances according to the virtual cycle time. So if synchronization is
required, operate the CX-Simulator in the computer cycle time.
High-speed Timer When executing a program in the computer cycle time, the High-speed Timer
and 1-ms Timer will not be guaranteed to operate correctly.
Interrupt Time when Online
Editing
When editing online by the CX-Simulator, the cycle time will not be affected
in the virtual cycle time. However, interrupt time will occur in the computer
cycle time as well as the actual CS/CJ-series PLC.