6 - 9
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-3 Operation Level
6
a-m
Auto/Manual Switch
The Event Input Assignment 1 to Event Input
Assignment 6 parameters must not be set to Auto/
Manual and the Auto/Manual Select Addition
parameter must be set to ON. The control must be
set to 2-PID control.
This parameter switches the Digital Controller between Automatic and Manual Modes.
If the O Key is pressed for at least 3 seconds when the Auto/Manual Switch parameter is
displayed, the Manual Mode will be entered and the manual control level will be
displayed.
This parameter will not be displayed if an event input is set to "MANU" (auto/manual).
Related Parameters
PID ON/OFF (Initial Setting Level): Page 6-45
Auto/Manual Select Addition (Advanced Function Setting Level): Page 6-75
m-sp
Multi-SP Set Point Selection
(Set Points 0 to 7)
The Number of Multi-SP Points parameter must not
be set to OFF and the Event Input Assignment 1 to
Event Input Assignment 6 parameters must not be
set to “Multi-SP No. switching bit 0” to “Multi-SP
No. switching bit 2.”
To use the multi-SP function, preset the eight set points (SP 0 to 7) in the Adjustment Level,
and then switch the set point either by operating the keys or by using external input signals
(event inputs).
This parameter is used to select set points 0 to 7.
rsp
Remote SP Monitor
There must be a remote SP input.
The ST (self-tuning) parameter must be set to OFF
(default: ON).
The Remote SP Enable parameter must be set to
ON (default: OFF).
This parameter is used to monitor the remote SP.
Related Parameters
SP Mode (Adjustment Level): Page 6-21
ST (self-tuning) (Initial Setting Level): Page 6-46
Remote SP Enable (Advanced Function Setting Level): Page 6-85
Remote SP Upper Limit (Advanced Function Setting Level): Page 6-86
Remote SP Lower Limit (Advanced Function Setting Level): Page 6-86
Operation
See
See
Function
000
Monitor
Monitor range Unit
Remote SP lower limit 10% to Remote SP upper limit +10% EU
See
See

Table of Contents

Other manuals for Omron E5CC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC and is the answer not in the manual?

Omron E5CC Specifications

General IconGeneral
BrandOmron
ModelE5CC
CategoryTemperature Controller
LanguageEnglish

Related product manuals