Input type: 5 (K thermocouple, −200°C to 1,300°C)
Control method: Floating control
SP ramp time unit: EU/min
Travel time: 45 s
SP ramp set value: 10 EU (°C)
Set point: 250°C
Setup Procedure
Power ON
Initial Setting Level
Set input
specifications
Set control
specifications
Set travel time.
Adjustment Level
Set SP ramp
Start operation
Power ON
Operation Level
PV/SP
Press the O Key for at least 3 s.
Control stops.
Initial Setting Level
Check input type.
Input Type:
Check that control
method is floating
control.
Floating control:
Use the U and D
Keys to set the
travel time to 45 s.
Close control:
Travel Time:
Press the O Key for at least 1 s.
Operation Level
Use the U and D
Keys to set the SP
to 250°C.
PV/SP:
Adjustment Level
SP Ramp Set
Value:
Press the O Key (for less than 1 s).
Press the O Key (for less than 1 s).
Control starts.
Operation Level
PV/SP:
Confirm that
control is running.
Running:
Stopped:
Start operation.
Operation Level
Use the U and D
Keys to set the SP
ramp set value to
10°C.
Set SP
An
s.err
error will be
displayed if the power
supply is turned ON
before the sensor is
connected.