5 - 55
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-18 Setting the PF Key
5
5-18-1 PF Setting (Function Key)
5-18 Setting the PF Key
*1 When AT cancel is specified, it means that AT is cancelled regardless of whether the AT currently being
executed is 100% AT or 40% AT.
*2 Alarms 1 to 4, the HB alarm, and the HS alarm are cancelled.
*3 For details on auto/manual operations using the PF Key, refer to 5-12 Performing Manual Control.
*4 AT-1 can be set for heating/cooling control or for floating position-proportional control, but the setting will be
disabled.
*5 The function that is set for the PF Key is disabled if the same function is assigned to an event input. For the
default event input assignments, refer to Event Input Assignment 1 to Event Input Assignment 6 on page
6-57.
Note1: Pressing the PF Key for at least one second executes operation according to the set value.
(However, if Digit Shift is set, operation will be in less than one second.) When the Monitor/Setting
Item parameter is selected, however, the display is changed in order from Monitor/Setting Item 1 to 5
each time the key is pressed.
2: This function is enabled when PF Key Protect is OFF.
5-18-1 PF Setting (Function Key)
PF Setting (Advanced
Function Setting Level)
• Pressing the PF Key for at least one second executes the operation set in the
PF Setting parameter. The default is shft (digit shift).
Set value Display Setting Function
OFF off Disabled Does not operate as a function key.
RUN run RUN Specifies RUN status.*5
STOP stop STOP Specifies STOP status.*5
R-S r-s
RUN/STOP reverse
operation
Specifies reversing the RUN/STOP operation status. *5
AT-2 at-2
100% AT
Execute/Cancel
Specifies reversing the 100% AT Execute/Cancel status.*1
*5
AT-1 at-1
40% AT
Execute/Cancel
Specifies reversing the 40% AT Execute/Cancel status.*1 *4
*5
LAT lat Alarm Latch Cancel Specifies canceling all alarm latches.*2 *5
A-M a-m Auto/Manual Specifies reversing the Auto/Manual status.*3 *5
PFDP pfdp
Monitor/Setting Item Specifies the monitor/setting item display. Select the monitor
setting item according to the Monitor/Setting Item 1 to 5
parameters (Advanced Function Setting Level).
SHFT shft Digit Shift
Operates as a Digit Shift Key when settings are being
changed.
shft
pf

Table of Contents

Other manuals for Omron E5DC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5DC and is the answer not in the manual?

Omron E5DC Specifications

General IconGeneral
BrandOmron
ModelE5DC
CategoryTemperature Controller
LanguageEnglish

Related product manuals