5 - 3
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-1 Shifting Input Values
5
5-1 Shifting Input Values
Shifting Inputs
You can set the Process Value Slope Coefficient and Process Value Input Shift parameters to
compensate the PV.
• Calculating the Process Value Slope Coefficient and Process Value Input Shift
In the following equation, PVi is the input to the calculation, PVo is the result, INRT is the process
value slope coefficient, and INS is the process value input shift: PVo = (PVi × INRT) + INS
Moving Average
• The moving average operation reduces sudden changes in the input due to noise and other
factors, and can be enabled separately for each input.
• The Moving Average Count parameter is used for the moving average. It can be set to OFF, 2, 4,
8, 16, or 32.
• The default is OFF (disabled).
* The default is 8 for models other than the E5@C-@-0@.
Parameter Setting range Unit Default
Process Value Input Shift
Temperature input: −199.9 to 999.9
°C or °F0.0
Analog input: −1,999 to 9,999
EU 0
Process Value Slope Coefficient
0.001 to 9.999
None 1.000
Parameter Setting range Unit Default
Moving Average Count OFF, 2, 4, 8, 16, or 32 Times OFF*
Input data
Operation result
Time