5 Advanced Operations
5 - 36
E5@C Digital Temperature Controllers User’s Manual (H174)
5-13 Using the Transfer Output for the
Process Value, Set Point, or other
Data
A transfer output can be used on models that have a transfer output. With the E5CC-U,* E5DC,*
E5DC-B, or E5GC, if the control output is a linear current output, the control output can be used as a
simple transfer output. For details on a simple transfer output, refer to 5-13-2 Simple Transfer Output
Function.
* The E5CC-U must be manufactured in May 2014 or later (version 2.2 or higher) and the E5DC must be
manufactured in July 2014 or later (version 2.2 or higher).
Precision and User Calibration
* For details on calibration, refer to Section 6 Parameters.
Transfer Output Signal (Initial Setting Level)
You can use the Transfer Output Signal parameter to specify whether to output a current or voltage
from the transfer output.
Terminal Arrangement
Transfer Output Type (Initial Setting Level)
You can use the Transfer Output Type parameter to specify any of six types of data to output.
*1 When the SP is selected, the remote SP will be output while the SP Mode parameter is set to the Remote SP
Mode.
5-13-1 Transfer Output Function
Precision User calibration
±0.3% FS Supported.*
Setting range Default
4-20: 4 to 20mA
4-20
1-5v: 1-5 V
Transfer output type Display Setting range
OFF (default) off ---
Set point
*1
sp
SP lower limit to SP upper limit
Set point during SP ramp sp-m SP lower limit to SP upper limit
PV
pV
Input setting range lower limit to input setting range upper limit or
Scaling lower limit to scaling upper limit
MV monitor (heating)
*2
mV
−5.0 to 105.0 (heating/cooling control: 0.0 to 105.0)
MV monitor (cooling)
*3
c-mV
0.0 to 105.0
Valve opening
*4
V-m
−10.0 to 110.0
Transfer output
Transfer output
E5CC
Option number: 006
E5EC/E5AC
Option number:
011, 012, 013, or 014
+
+
−
V
I
+
+
−
V
I
31
33
32
E5CC-B
Option number: 006
E5EC-B
Option number: 011 or 014
+
+
−
V
I
22
23
24
+
+
−
V
I
42
43
44
P
R
Q
Transfer output
Transfer output