Page #173 background image
4 - 31
4 Basic Operation
E5@C Digital Temperature Controllers User’s Manual (H174)
4-9 Determining PID Constants (AT, ST, Manual Setup)
4
4-9-4 Manual Setup
When P (Proportional Band) Is Adjusted
When I (Integral Time) Is Adjusted
When D (Derivative Time) Is Adjusted
Increased
The curve rises gradually, and a long stabilization time
is created, but overshooting is prevented.
Decreased
Overshooting and hunting occur, but the set value is
quickly reached and the temperature stabilizes.
Increased
It takes a long time to reach the set point.
It takes time to achieve a stable state, but overshooting,
undershooting, and hunting are reduced.
Decreased
Overshooting and undershooting occur.
Hunting occurs.
The Digital Controller starts up faster.
Increased
Overshooting, undershooting, and stabilization times
are reduced, but fine hunting occurs on changes in the
curve itself.
Decreased
Overshooting and undershooting increase, and it takes
time to return to the set point.
Set
value
Set
value
Set
value
Set
value
Set
value
Set
value

Table of Contents

Other manuals for Omron E5DC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5DC and is the answer not in the manual?

Omron E5DC Specifications

General IconGeneral
BrandOmron
ModelE5DC
CategoryTemperature Controller
LanguageEnglish

Related product manuals