6 - 37
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-4 Adjustment Level
6
w1 to 8on
w1 to 8of
Work Bit 1 to 8 ON Delay
Work Bit 1 to 8 OFF Delay
The work bit operation type must not be set to OFF.
• ON Delay
When the results of a work bit logic operation is ON, the work bit is turned ON after the
time specified in the parameter elapses.
• OFF Delay
When the results of a work bit logic operation is OFF, the work bit is turned OFF after the
time specified in the parameter elapses.
Related Parameters
Auxiliary Output 1 to 4 Assignment (Advanced Function Setting Level): Page 6-82
plcm
Communications Monitor
Communications must be supported.
The Protocol Setting parameter must be set to Host
Link (FINS) or the MC Protocol.
• The Communications Monitor parameter displays the communications cycle time of the
E5@C.
• If communications are not possible with the PLC, c.err is displayed. When
communications are restored, the cycle time is displayed again.
Also refer to the E5
@
C Digital Controllers Communications Manual (Cat. No. H175) for
information on communications.
Setting range Unit Default
0 to 999 Seconds 0
Monitoring range Default
Normal: 0 to 9999 ms, If 9999 ms is exceeded: ]]]]
Error: c.err
---