6 - 37
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-4 Adjustment Level
6
w1 to 8on
w1 to 8of
Work Bit 1 to 8 ON Delay
Work Bit 1 to 8 OFF Delay
The work bit operation type must not be set to OFF.
ON Delay
When the results of a work bit logic operation is ON, the work bit is turned ON after the
time specified in the parameter elapses.
OFF Delay
When the results of a work bit logic operation is OFF, the work bit is turned OFF after the
time specified in the parameter elapses.
Related Parameters
Auxiliary Output 1 to 4 Assignment (Advanced Function Setting Level): Page 6-82
plcm
Communications Monitor
Communications must be supported.
The Protocol Setting parameter must be set to Host
Link (FINS) or the MC Protocol.
The Communications Monitor parameter displays the communications cycle time of the
E5@C.
If communications are not possible with the PLC, c.err is displayed. When
communications are restored, the cycle time is displayed again.
Also refer to the E5
@
C Digital Controllers Communications Manual (Cat. No. H175) for
information on communications.
000
000
Function
Setting
Setting range Unit Default
0 to 999 Seconds 0
See
See
Function
Setting
Monitoring range Default
Normal: 0 to 9999 ms, If 9999 ms is exceeded: ]]]]
Error: c.err
---

Table of Contents

Other manuals for Omron E5DC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5DC and is the answer not in the manual?

Omron E5DC Specifications

General IconGeneral
BrandOmron
ModelE5DC
CategoryTemperature Controller
LanguageEnglish

Related product manuals