6-8 Advanced Function Setting Level
6
rs-t
Remote SP Input
There must be a remote SP input.
The ST (self-tuning) parameter must be set to OFF
(default: ON).
This parameter sets the input type for the remote SP.
Related Parameters
ST (self-tuning) (Initial Setting Level): Page 6-46
rspu
Remote SP Enable
There must be a remote SP input.
The ST (self-tuning) parameter must be set to OFF
(default: ON).
This parameter is set to ON to enable setting SP Mode. You can set the SP Mode parame-
ter to LSP to select a local SP or to RSP to select a remote SP. If this parameter is set to
OFF, only a local SP can be used.
Related Parameters
SP Mode (Adjustment Level): Page 6-21
ST (self-tuning) (Initial Setting Level): Page 6-46
Setting
Setting range Default
4-20: 4 to 20mA
4-20
0-20: 0 to 20mA
1-5v: 1 to 5V
0-5v: 0 to 5V
0-10: 0 to 10V
Setting range Default
on: Enabled or off: Disabled off