A Appendices
A - 24
E5@C Digital Temperature Controllers User’s Manual (H174)
Symptom: Cannot Communicate or a Communications Error Occurs
* Also refer to the E5
@
C Digital Controllers Communications Manual (Cat. No. H175) for details on
errors.
Meaning Countermeasures
The communications wiring is not correct. Correct the wiring.
The communications line has become
disconnected.
Connect the communications line securely and tighten the screws.
The communications cable is broken. Replace the cable.
The communications cable is too long. The total cable length for RS-485 is 500 m max.
The wrong communications cable has
been used.
Use shielded twisted-pair cable for the communications cable. For detailed
wire specifications, refer to 2-2-9 Precautions when Wiring.
More than the specified number of
communications devices are connected to
the same communications path.
When 1:N communications are used, a maximum of 32 nodes may be
connected, including the host node.
An end node has not been set at each end
of the communications line.
Set or connect terminating resistance at each end of the line. If the E5@C
is the end node, 120-Ω (1/2-W) terminating resistance is used. Be sure
that the combined resistance with the host device is 54 Ω minimum.
The specified power supply voltage is not
being supplied to the Digital Controller.
Supply the specified power supply voltage.
The specified power supply voltage is not
being supplied to an Interface Converter
(such as the K3SC).
Supply the specified power supply voltage.
The same baud rate and communications
method are not being used by all of the
Digital Controllers, host devices, and other
devices on the same communications line.
Set the same values for the baud rate, protocol, data length, stop bits, and
parity on all nodes.
The unit number specified in the
command frame is different from the unit
number set by the Digital Controller.
Use the same unit number.
The same unit number as the Digital
Controller is being used for another node
on the same communications line.
Set each unit number for only one node.
There is a mistake in programming the
host device.
Use a line monitor to check the commands. Check operation using a
sample program.
The host device is detecting the absence
of a response as an error before it
receives the response from the Digital
Controller.
Shorten the send data wait time in the Digital Controller or increase the
response wait time in the host device.
The host device is detecting the absence
of a response as an error after
broadcasting a command.
The Digital Controller does not return responses for broadcast commands.
The host device sent another command
before receiving a response from the
Digital Controller.
The response must always be read after sending a command (except for
broadcast commands).
The host device sent the next command
too soon after receiving a response from
the Digital Controller.
After receiving a response, wait at least 2 ms before sending the next
command.
The communications line became
unstable when Digital Controller power
was turned ON or interrupted, and the
host device read the unstable status as
data.
Initialize the reception buffer in the host device before sending the first
command and after turning OFF the power to the Digital Controller.
The communications data was corrupted
from noise from the environment.
Try using a slower baud rate.
Separate the communications cable from the source of noise.
Use a shielded, twisted-pair cable for the communications cable.
Use as short a communications cable as possible, and do not lay or loop
extra cable.
To prevent inductive noise, do not run the communications cable parallel to
a power line.
If noise countermeasures are difficult to implement, use an Optical
Interface.

Table of Contents

Other manuals for Omron E5DC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5DC and is the answer not in the manual?

Omron E5DC Specifications

General IconGeneral
BrandOmron
ModelE5DC
CategoryTemperature Controller
LanguageEnglish

Related product manuals