4 Basic Operation
4 - 50
E5@C Digital Temperature Controllers User’s Manual (H174)
4-13 Customizing the PV/SP Display
The following table shows the contents of the No. 1, 2, and 3 displays, according to the setting of the
PV/SP Display Screen Selection parameter.
The following table shows the contents of the No. 1, 2, and 3 displays, according to the setting of the
PV/SP Display Screen Selection parameter in the Advanced Function Setting Level.
* The set value of the Alarm Value 1 parameter is displayed even if it is not valid due to the setting of the
Alarm 1 Type parameter.
During temperature input, the decimal point position depends on the currently selected sensor, and
during analog input it depends on the Decimal Point parameter setting.
PV/SP Display Selections
* The default is 1 for models other than the E5@C-@-0@.
MV Displays for Heating and Cooling Control (Not Supported for
Position-proportional Models.)
Select either the manipulated variable for heating or the manipulated variable for cooling as the MV
to be displayed for PV/SP/MV during heating and cooling control. The MV Display Selection
parameter is displayed only when heating/cooling control is being performed and PV/SP/MV is
selected in the PV/SP Display Screen parameter or a Monitor/Setting Item Display parameter.
4-13-1 PV/SP Display Selections
Set value No. 1 display No. 2 display
No. 3 display
(E5EC, E5EC-B, and E5AC Only)
0 Nothing is displayed. Nothing is displayed. Nothing is displayed.
1 PV SP Nothing is displayed.
2 PV Nothing is displayed. Nothing is displayed.
3 SP SP (character display) Nothing is displayed.
4PVSPMV
(Valve opening for Position-proportional
Models)
5PVSPMulti-SP No.
6PV SP
Soak Time Remain
7 PV SP Internal Set Point (ramp SP)
8PVSPAlarm Value 1*
Monitoring range Unit
PV
Temperature input: The specified range for the specified sensor.
Analog input: Scaling lower limit −5%FS to Scaling upper limit +5%FS
EU
Setting (monitoring) range Unit
SP SP lower limit to SP upper limit EU
Code Parameter Default Level
spd1 PV/SP No. 1 Display Selection 4* Advanced Function Setting
Level
spd2 PV/SP No. 2 Display Selection 0