A Appendices
A - 32
E5@C Digital Temperature Controllers User’s Manual (H174)
*1 When the Manual MV Limit Enable parameter is set to ON, the setting range will be the MV lower limit to the MV upper
limit.
*2 The valve opening is monitored for floating control or for close control with the Direct Setting of Position-proportional MV
parameter set to OFF.
The contents displayed vary depending on the Monitor/Setting 1 to 5 (advanced function setting
level) setting.
A-6-4 Manual Control Level
Parameters Setting (monitor) value Default Unit
Manual MV
−5.0 to 105.0 (standard)
*1
−105.0 to 105.0 (heating/cooling)
*2
−5.0 to 105.0 (position-proportional)
*1*2
0.0 %
A-6-5 Monitor/Setting Item Level
A-6-6 Advanced Function Setting Level
Parameters Characters Setting (monitor) value Display Default Unit
Parameter Initialization init OFF, FACT off, fact OFF None
Number of Multi-SP
Points
mspu OFF(1), 2 to 8 off, 2 to 8 OFF None
SP Ramp Time Unit spru S: EU/second
M: EU/minute
H: EU/hour
s, m, h MNone
Standby Sequence
Reset
rest Condition A, condition B a, b Condition A None
Auxiliary Output 1
Open in Alarm
sb1n N-O: Close in alarm
N-C: Open in alarm
n-o, n-c N-O None
Auxiliary Output 2
Open in Alarm
sb2n N-O: Close in alarm
N-C: Open in alarm
n-o, n-c N-O None
Auxiliary Output 3
Open in Alarm
sb3n N-O: Close in alarm
N-C: Open in alarm
n-o, n-c N-O None
Auxiliary Output 4
Open in Alarm
sb4n N-O: Close in alarm
N-C: Open in alarm
n-o, n-c N-O None
HB ON/OFF hbu OFF, ON off, on ON None
Heater Burnout Latch hbl OFF, ON off, on OFF None
Heater Burnout
Hysteresis
hbh 0.1 to 50.0 0.1 A
ST Stable Range st-b 0.1 to 999.9 15.0 °C or °F
α alfa 0.00 to 1.00 0.65 None
Integral/Derivative
Time Unit
tidu 1, 0.1 1, 0.
1 1 Second
AT Calculated Gain at-g 0.1to 10.0 Standard
Model: 0.8
Po
sition-pro
portional
Model: 1.0
None
AT Hysteresis
at-h Temperature input: 0.1 to 999.9 0.8 °C or °F
Analog input: 0.01 to 9.99 0.20 %FS
Limit Cycle MV
Amplitude
lcma 5.0 to 50.0 20.0 %
Input Digital Filter inf 0.0 to 999.9 0.0 Second
Moving Average Count mav OFF, 2, 4, 8, 16, or 32
OFF
*5
Times
FB Moving Average
Count
*9
pmav OFF, 2, 4, 8, 16, or 32 16 Times
MV Display o-dp OFF, ON off, on OFF None
Automatic Display
Return Time
ret OFF, 1 to 99 off, 1 to 99 OFF Second