9 Connecting to Allen-Bradley (Rockwell) PLC
9-16
NB-series Programmable Terminals Host Connection Manual (V108)
9-5 Cable Fabrication
RS232 Communication Cable for MicroLogix
• Communication Cable (Cat.No.: 1761-CBL-PM02) manufactured by Rockwell Automation, Inc.
• ALC +Advanced Interface Converter (Cat.No.:1761-NTE-AIC) and RS232 Communication Cable
RS232 Communication Cable for SLC 5 / 03
RS232 Communication Cable for CompactLogix/ControlLogix
Use Twisted Pair Cable to connect. Refer to Ethernet communication specifications in A-1-3 Communi-
cation Specifications in the NB-series Programmable Terminals Setup Manual (Cat. No. V107).
Serial Communication Cable
Ethernet Communication Cable
PT (COM1/COM2)
Pin No.
2
3
9
Signal
SD
RD
SG
D-Sub
9Pin
(Female)
PLC
Pin No.
3
2
5
Signal
RXD
TXD
SG
7
8
RTS
CTS
D-Sub
9Pin
(Female)
PT (COM1/COM2)
Pin No.
2
3
9
Signal
SD
RD
SG
D-Sub
9Pin
(Female)
Micrologix series AIC-terminal
Pin No.
2
3
5
Signal
RXD
TXD
GND
D-Sub
9Pin
(Female)
PT (COM1/COM2)
Pin No.
2
3
9
Signal
SD
RD
SG
D-Sub
9Pin
(Female)
PLC
Pin No.
2
3
5
Signal
RXD
TXD
GND
D-Sub
9Pin
(Female)
PT (COM1/COM2)
Pin No.
2
3
9
Signal
SD
RD
SG
D-Sub
9Pin
(Female)
PLC CH0/CH1 terminal
Pin No.
2
3
5
Signal
RXD
TXD
GND
D-Sub
9Pin
(Male)