Appendix 3 Using NS-AL002 Converters
Preparing the Shield of RS-422A/485 Connectors
Always prepare RS-422A/485 cable shields properly. Otherwise, communications errors
may occur with the host.
Ground only one end of the shield when connecting the ground terminal (GR) of the de-
vices to the functional ground (FG: ), and grounding each signal line at only one point
and to 100
max, as shown in Figure (a).
Ground both ends of the shield when not grounding the functional ground (FG: ) of the
PT, as shown in Figure (b).
When using the CJ1W-CIF11 or when using the NT-AL001/NS-AL002 together with the
CJ1W-CIF11, always performs connections, shield processing, and grounding as shown in
Figure (b).
A-22