5 - 51
5 Setup and Wiring
Vision System FH/FZ5 series Hardware Setup Manual (Z366)
5-8 Installation in a Control Panel
5
5-8-5 FZ5-L Series
Precautions for Correct Use
Ambient Temperature
Install and store the product in a location that meets the following conditions:
Surrounding temperature of 0 to 50°C (-20 to +65°C in storage)
Relative humidity of between 35 to 85%RH
Do not let the ambient temperature exceed 50°C (122°F).
Provide a forced-air fan cooling or air conditio
ning if the ambient temperature is near 50°C
(122°F) so that the ambient temperature never exceeds 50°C (122°F).
Installation method
For good heat dissipation, install the product o
nly in the position shown below so as not to
block the ventilation holes.
Do not install the product in the following positions.
For good ventilation, provide a clearance of 50 mm
or more above the sensor controller away
from other devices in the normal floor mounting. For the right and left sides, provide a clear-
ance of 30 mm or more, and for the back side, 15
mm or more. These clearances are also
required when mounting multiple sensor controllers side by side. For the back mounting, the
back-side clearance of 15 mm is nor required.
5-8-5 FZ5-L Series

Table of Contents

Other manuals for Omron SYSMAC FH Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC FH Series and is the answer not in the manual?

Omron SYSMAC FH Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC FH Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals