EasyManuals Logo
Home>Pulsafeeder>Controller>MicroVision

Pulsafeeder MicroVision User Manual

Pulsafeeder MicroVision
43 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
72-910-16 Rev. N
Page 33 of 43
9. Factory Defaults
Parameter
Default
Configuration
Date Format
MM/DD/YY
Time Format
12hr Clock
Water Meter Type
Dry Contact
Water Meter Pulse Volume
100
Water Meter Units
Gallons
Drum Levels
Pumps Run
Display Dampener
1 Second
Rise/Fall Setpoint
Rising
Display Contrast
26
Password
0000(disabled)
Language
English
Settings
Conductivity Setpoint
1500
Conductivity Differential
50
Conductivity Limit Timer
00:00(disabled)
Alarm Setpoint
Track Setpoint/200us
4-20ma Low Range
0
4-20ma High Range
9999
Inhibitor Feed Mode
Limit Timer
Inhibitor Limit Timer
1-hour, 30-minutes
Inhibitor Biocide Tracking
None
Biocide A and B Days/Weeks
All Days/All weeks
Biocide A and B Start Times
00:00(disabled)
Biocide A and B Feed Time
1-minute
Biocide A and B Pre-Bleed Time
00:00(disabled)
Biocide A and B Pre-Bleed Conductivity
Minimum
1475
Biocide A and B Bleed Lockout
00:00(disabled)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsafeeder MicroVision and is the answer not in the manual?

Pulsafeeder MicroVision Specifications

General IconGeneral
BrandPulsafeeder
ModelMicroVision
CategoryController
LanguageEnglish

Related product manuals