2 Troubleshooting Guide
The electronic control board LEDs help with wiring and troubleshooting diagnostics. Every LED indicates the status of
the door. The electronic control board has a non-volatile memory and the LEDs return to their initial state after a
power interruption.
Easy Fix: Before starting any intervention, verify the LED's monitoring status and refer to Table 4, p.20 for a
proper diagnosis.
Table 10 - Troubleshooting Guide - Part 1
Symptom Probable Cause Suggested Action
Door doesn't respond
to any command
“Stop” button is stuck. (LED D9 is OFF) Press and release any “Stop”
button.
Control station not connected or wired correctly.
(LED D9 is OFF)
Verify and correct wiring.
No power supply. (LED D2 is OFF) Verify the incoming power line
from the main breaker, making sure
it has not tripped or blown a fuse.
Door closes only by
constant pressure
Selector switch set on C2 mode. Set switch on B2 mode (B2=1).
Photo cells are not properly aligned or are
obstructed. (LED D4 is ON)
Clear the obstruction or re-align.
Faulty monitored photo cells or loose wires.
(LED D4 is ON)
Verify, tighten or replace.
Reversing device not connected (Monitored
photo cell as per UL325). (LED D4 is ON)
Connect monitored photo cells
as per UL325 for momentary
contact to close.
Loop is obstructed (Presence of metal).
(LED D10 is ON)
Clear the obstruction.
Operator not operating
as expected
Selector switch is not set on the desired mode. Set switch on desired mode,
refer to p.22 for further details.
Timer to Close doesn't
close the door
Timer to Close has been suspended
accidentally for ONE cycle.
Timer to Close will return to
normal after door have been fully
closed. Refer to p.23 for further
details.
Door doesn't respond to
any radio command
No power supply (Transmitter light is OFF) Replace the transmitter's
battery.
Transmitter is not properly programmed. Reprogram transmitter.
Photo cells are not properly aligned or are
obstructed. (LED D4 is ON)
Clear the obstruction or re-align.
“Stop” button doesn’t
stop the door
Two 3-push button stations (or more) are
connected in parallel.
Verify and correct wiring.(Stop
buttons in series, only Open &
Close in parallel).
For technical support, please call 1-800-4-Raynor (1-800-472-9667) or visit www.raynor.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raynor ControlHoist CMT and is the answer not in the manual?

Raynor ControlHoist CMT Specifications

General IconGeneral
BrandRaynor
ModelControlHoist CMT
CategoryDoor Opening System
LanguageEnglish

Related product manuals