8 Troubleshooting
8
40 Rittal Liquid Cooling Package
8.3 List of error messages and solutions
Alarm code Display Possible cause Possible solution
ALA02 Alarms ALA02
Position: B2
Probe B2 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA03 Alarms ALA03
Position: B3
Probe B3 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA04 Alarms ALA04
Position: B4
Probe B4 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA06 Alarms ALA06
Position: B6
Probe B6 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA07 Alarms ALA07
Position: B7
Probe B7 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA08 Alarms ALA08
Position: B8
Probe B8 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA09 Alarms ALA09
Position: B9
Probe B9 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA10 Alarms ALA10
Position: B10
Probe B10 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA11 Alarms ALA11
Position: B11
Probe B11 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALA12 Alarms ALA12
Position: B12
Probe B12 faulty or disconnected
alarm
Sensor failure or sensor not cor-
rectly connected.
Check the connection on the moth-
erboard or replace the sensor.
ALB01 Alarms ALB01
Position: ID3
High pressure
High ambient temperature, incor-
rect coolant filling, defective fan.
Check device limits, check coolant
volume and check correct function-
ing of fan.
ALB02 Alarms ALB02
High pressure compressor 1 by
transducer
High ambient temperature, incor-
rect coolant filling, defective fan.
Check device limits, check coolant
volume and check correct function-
ing of fan.
ALB03 Alarms ALB03
Low pressure compressor/com-
pressors by transducer
Incorrect coolant filling, insuffi-
cient quantity of coolant, blocked
coolant lines, thermostatic valve
closed.
Check coolant volume, check lines
for leaks, check thermostatic valve.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rittal LCP Rack DX 12 and is the answer not in the manual?

Rittal LCP Rack DX 12 Specifications

General IconGeneral
BrandRittal
ModelLCP Rack DX 12
CategoryAir Conditioner
LanguageEnglish

Related product manuals