18 Rockwell Automation Publication 750-PM101B-EN-P - April 2022
Chapter 2 Parameter Organization
what ports 9 and 10 contain. Ports 9 and 10 do not display parameters or
software that is related to unused configurations. For example, if you do not
select Torque Prove in the Application Selection parameter then port 9 does
not contain parameters for Torque Prove. If you do not select the Flux Vector
motor control mode, then port 10 does not display Flux Vector parameters or
software.
Port 9 Application Parameters
This port contains parameters and software that is related to specific
applications. The contents of this port depend the setting of parameter 0:70
[Application Sel]. It can contain nothing, Process PID, Torque Prove, or Oil
Well Pump. If enabled in parameter 0:72 [Emb Logic Select], port 9 will also
display DeviceLogix parameters.
Port 10 Primary and Port 11 Secondary Motor Side Control Parameters
These ports contain parameters and software that is related to the primary and
secondary control of the motor side inverter. Port 10 is the primary motor side
control port and port 11 is the secondary port. The contents of these ports
depend the setting of parameters 0:65 [Pri MtrCtrl Mode] and 0:67 [Sec
MtrCtrl Mode]. They can contain Volts per Hertz, Sensorless Vector,
Economizer, or Flux Vector control. They contain parameters for configuring
the starting and stopping of the motor side inverter. They contain parameters
for entering the electrical attributes of the motor. They contain parameters for
configuring and monitoring the Position, Velocity, and Torque loops.
Port 12 Motor Side Power Parameters—PowerFlex 755T Products
This port contains parameters that are related to the power hardware in the
motor side inverter. These parameters monitor and configure the power
modules.
Port 13 Line Side Control Parameters—PowerFlex 755T Products
This port contains parameters and software that is related to control of the line
side converter. It contains parameters for configuring and monitoring the
control of the converter. It contains parameters for entering the electrical
attributes of the AC line source.
Port 14 Line Side Power Parameters—PowerFlex 755T Products
This port contains parameters that are related to the power hardware in the
line side converter. These parameters monitor and configure the power
modules, AC precharge, and LCL filters.