EasyManuals Logo
Home>Rockwell Automation>Industrial Equipment>B Series

Rockwell Automation B Series User Manual

Rockwell Automation B Series
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #118 background imageLoading...
Page #118 background image
118 Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Chapter 3 Programming and Parameters
Advanced Program Group (continued)
A437 [DB Resistor Sel] Related Parameter(s): A438, A550
Stop drive before changing this parameter.
Enables/disables external dynamic braking and selects the level of resistor protection.
Options 0 “Disabled” (Default)
1 “Norml RA Res” 5%
2 “NoProtection” 100%
3...99 “3...99% DutyCycle”
When A437 [DB Resistor Sel] is set to a value greater than “0”, the value set in parameter A550 [Bus Reg Enable] will not take effect.
A438 [DB Threshold] Related Parameter(s): A437
Sets the DC bus voltage threshold for Dynamic Brake operation. If DC bus voltage rises above this level, Dynamic Brake turns on. Lower values makes the dynamic braking function more
responsive but may result in nuisance Dynamic Brake activation (IGBT can modulate continuously).
Values Default: 100.0%
Min/Max: 10.0/110.0%
Display: 0.1%
ATTENTION: Equipment damage may result if this parameter is set to a value that causes the dynamic braking resistor to dissipate excessive power. Parameter
settings less than 100% should be carefully evaluated to ensure that the Dynamic Brake resistor's wattage rating is not exceeded. In general, values less than
90% are not needed. This parameter's setting is especially important if parameter A437 [DB Resistor Sel] is set to 2 “NoProtection.
A439 [S Curve %]
Enables a fixed shape S-Curve that is applied to the acceleration and deceleration ramps (including jog).
S-Curve Time = (Accel or Decel Time) x (S-Curve Setting in percentage)
Values Default: 0%
Min/Max: 0/100%
Display: 1%
S-Curve Time
Total Time to Accelerate = Accel Time + S-Curve Time
50% S-Curve
Target
vel
Target
vel/2
S-Curve Time = Accel Time
Total Time to Accelerate = Accel Time + S-Curve Time
100% S-Curve
Target
vel
Example:
Accel Time = 10 s
S-Curve Setting = 30%
S-Curve Time = 10 x 0.3 = 3 s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation B Series and is the answer not in the manual?

Rockwell Automation B Series Specifications

General IconGeneral
BrandRockwell Automation
ModelB Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals