10 Rockwell Automation Publication DRIVES-AT005D-EN-P - May 2022
Chapter 1 DC Bus Wiring Guidelines
DC Bus Connections
The interconnection of drives to the DC bus, and the inductance levels between the drives, must be kept to a minimum for optimum system
operation.
Bus Bar Versus Cable
Continuous bus bar is required. When using cables to connect drives to the system bus within a cabinet, adhere to the following guidelines:
Keep the cable lengths as short as possible.
Twist cable where possible, approximately one twist per foot.
Use cable that is appropriately rated for the voltage class of the product.
The DC bus connections can’t be ‘daisy chained’. Use a ‘star’ configuration of the DC bus connections as shown in Figure 2
to accommodate
proper fusing.
Figure 2 - Star Configuration of Common Bus Connections
WARNING: The incorrect use or configuration of third-party assemblies can result in
reduced system reliability and drive damage.
L1
L2
L3
DC+
DC+
DC-
DC-
BR1 BR2
M1
L1
L1
L2
L2
L3
L3
DC+
DC-
BR1 BR2
M2
L1
L2
L3
DC+
DC-
BR1 BR2
M3
DC+ DC–
Power Distribution
Terminal Block or Bus Bar
Bus Supply
AC Drive 1
AC Drive 2
AC Drive 3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 755TM and is the answer not in the manual?

Rockwell Automation PowerFlex 755TM Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 755TM
CategoryDC Drives
LanguageEnglish

Related product manuals