54 Rockwell Automation Publication DRIVES-AT005D-EN-P - May 2022
Appendix A Electrical Ratings, Recommended Protective Devices, and DC Bus Capacitance
Circuit Protection Configurations
The following diagrams illustrate the AC and DC circuit protection configurations for the products that are listed in the previous table.
Terms used in the diagrams:
CB - Circuit Breaker. For branch circuit overload and overcurrent protection as well as disconnection of AC power. See PowerFlex 750-Series
Products with TotalFORCE Control Technical Data, publication 750-TD100
, fuse and circuit breaker data tables for fuse specifications.
ST - Shunt Trip. Part of CB, applying power trips the circuit breaker
N - AC Contactor. Three pole AC contactor for disconnecting AC power.
DS - Disconnect Switch. For user disconnection of AC or DC power.
FU - AC Fuse. Dual element time delay or non-time delay fuse. Optional for branch circuit overload and overcurrent protection. See PowerFlex 750-
Series Products with TotalFORCE Control technical data manual, publication 750-TD100
, fuse and circuit breaker data tables for fuse specifications.
SPF - Semiconductor Protection Fast Acting Fuse. Required for protection of power electronics. These fuses are typically located within the
PowerFlex product. The exception is PowerFlex 755TL/TR Frames 5…6 AC drives and PowerFlex 755TM Frame 6 Regenerative Bus Supply.
P/C - Pre-charger. Resistive or SCR phase-controlled circuits for precharging DC bus capacitors.
C - DC Bus Capacitors.
PowerFlex 755TM Non-regenerative Supply, All Configurations
See the PowerFlex 755TM Non-Regenerative Supply User Manual, publication 750-UM100, for recommended external AC input overload/over-current
protective devices.
C
CB
AC
Line
AC
Line
DS
FU
- OR -
Bus Supply Converter
P/C
SPF
SPF
opt
+DC
-DC
PowerFlex 755TM Non-regenerative Supply
DC
Bus

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 755TM and is the answer not in the manual?

Rockwell Automation PowerFlex 755TM Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 755TM
CategoryDC Drives
LanguageEnglish

Related product manuals