Analog value processing
C.4 Representation of output ranges
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
185
Representation of output ranges
The tables below set out the digitalized representation of the output ranges separately for
bipolar and unipolar ranges. The resolution is 16 bits.
Table C- 16 Bipolar output ranges
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
32511 117.589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Maximum output
Overrange
Nominal range
Underrange
-32512 -117.593 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 Minimum output
* When values > 32511 are specified, the
output value is limited to 117.589%.
** When values < -32512 are specified, the output value is limited to -117.593%.
Table C- 17 Unipolar output ranges
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
32511 117.589 0 1 1 1 1 1 1 1 x x x x x x x x Maximum output
value*
Overrange
27649 100.004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1
Nominal range
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Minimum output
* When values > 32511 are specified, the output value is limited to 117.589%.