53 / 66
Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en
Building Technologies Handling 14 Dec 2011
When an electric heater is connected directly to output Y21, the rated current of
the electric heating should be entered in parameter 46
(RDG110 only, device
index D and higher)
, see section 4.8.
Default setting: 1 A for loads
1 A.
We recommend to review the setpoints and setpoint setting ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy
5.2 Operation
See also Operating Instructions B3181 enclosed with the thermostat.
Layout
RDG100
RDG110
RDG140
RDG160
RDG100T
RDG100T/H
1 Operating mode button / Esc
2 Button to enter the time and to set the timers
3 Fan mode button / OK
4 Rotary knob for setpoint and parameter adjustment
When the thermostat is in normal operation, the actual operating mode and
status are indicated by symbols
When a button is pressed, the thermostat goes into mode selection.
The backlit LCD will turn on, all possible mode selection options (symbols) will
turn on, indicator element (arrow) will appear on the current mode/status
When the button is pressed again, the indicator element will change to the next
mode symbol and so on.
After the last press and a timeout of 3 seconds, the newly selected mode is
confirmed, the other elements disappear
After a timeout of 20 seconds, the LCD backlight will turn off
Adaptive temperature
compensation for el.
heater
Setpoint and setpoint
setting range limitation
Button operation
1
4
2
1
3
4
1
2
4
3