Product overview
3
3.1 Properties of I/O module
De󹪝nition
The I/O module F-AI 8xI 2-/4-wire HART HA is an analog input module with 8 current inputs for
process control.
In addition to the technical speci󹪝cations, this module has the following properties:
Fail-safe analog module
PROFIsafe pro󹪝le V2.6.1
PROFIsafe address type 2
8 fail-safe analog inputs (up to SIL3/Cat.3/PLd or SIL3/Cat.4/PLe with CPU voting)
Measuring range: 0..20 mA and 4..20 mA
Resolution: 16 bits including sign
Short-circuit proof internal sensor supply Uv for 2-wire transmitter
External sensor supply possible
Con󹪝gurable diagnostics
Diagnostics display LED DIAG (red/green)
Maintenance messages and maintenance display LED MT (yellow)
Channel-speci󹪝c status display LED "Channel status" (green)
Channel-speci󹪝c fault display LED "Channel fault" (red)
Diagnostics
e.g. short-circuit/ wire break, channel-by-channel
e.g. supply voltage missing, module-by-module
Channel-wide and module-wide passivation
HART communication (Rev. 5 to Rev. 7)
The module supports the following functions:
Firmware upgrade
I&M identi󹪝cation data
Value status
IO redundancy
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA 11

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP HA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP HA and is the answer not in the manual?

Siemens SIMATIC ET 200SP HA Specifications

General IconGeneral
CategoryI/O Systems
SystemSIMATIC ET 200SP HA
MountingDIN rail
Protection RatingIP20
Communication ProtocolPROFINET
RedundancyYes
Hot SwappingYes
ModularityModular
Power Supply24 V DC
Temperature Range-40 to 70 °C
Product TypeDistributed I/O
Number of I/O modulesUp to 64
Redundancy Typesystem redundancy
Operating Temperature-40 to 70 °C
Storage Temperature-40 to 70 °C
Relative Humidity5% to 95% (non-condensing)
Vibration ResistanceIEC 60068-2-6