Both redundant modules measure the process simultaneously and independently. Similarly,
both redundant modules form diagnostics, interrupts and process values.
The HART communication takes place exclusively via one of the two redundant channels.
Description
The acquired process value is made available on both the modules in error-free, redundant
operation.
IO redundancy is only possible with the I/O module F-AI 8xI 2-/4-wire HART HA with the terminal
block type F1 ("TB45R-P32"; 6DL1193-6TP00-0DF1).
5.4.15 Interference frequency suppression
De󹪝nition
Suppresses the interference that is caused by the frequency of the AC voltage network used.
The following parameter assignments are possible:
50 Hz (integration time 20 ms)
60 Hz (integration time 16.6 ms)
When 50 Hz is set, the 400 Hz interfering signals are also 󹪝ltered automatically.
5.4.16 Behavior after channel fault
De󹪝nition
With this parameter you specify whether the entire F-module is passivated after channel faults
or just the faulty channels:
"Passivate entire module"
"Passivate channel"
Parameters/address space
5.4 Explanation of the module/channel parameters
F-AI 8xI 2-/4-wire HART HA
34 Equipment Manual, 09/2021, A5E50557845-AA

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP HA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP HA and is the answer not in the manual?

Siemens SIMATIC ET 200SP HA Specifications

General IconGeneral
CategoryI/O Systems
SystemSIMATIC ET 200SP HA
MountingDIN rail
Protection RatingIP20
Communication ProtocolPROFINET
RedundancyYes
Hot SwappingYes
ModularityModular
Power Supply24 V DC
Temperature Range-40 to 70 °C
Product TypeDistributed I/O
Number of I/O modulesUp to 64
Redundancy Typesystem redundancy
Operating Temperature-40 to 70 °C
Storage Temperature-40 to 70 °C
Relative Humidity5% to 95% (non-condensing)
Vibration ResistanceIEC 60068-2-6
Shock ResistanceAccording to IEC 60068-2-27
Mounting TypeDIN rail