Analog value processing
C.3 Representation of input ranges
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
180 Manual, 09/2016, A5E35306440-AB
C.3.1
Representation of analog values in voltage measuring ranges
The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table C- 6 Voltage measuring ranges ±10 V, ±5 V
Values
Voltage measuring range
Range
dec.
hex.
±10 V
±5 V
32767 7FFF >11.759 V >5.879 V Overflow
32511
7EFF
11.759 V
5.879 V
Overrange
27649 6C01
27648
6C00
10 V
5 V
Nominal range
20736
5100
7.5 V
3.75 V
1
1
361.7 µV
180.8 µV
0
0
0 V
0 V
-1
FFFF
-20736
AF00
-7.5 V
-3.75 V
-27648
9400
-10 V
-5 V
-27649
93FF
Underrange
-32512
8100
-11.759 V
-5.879 V
-32768
8000
<-11.759 V
<-5.879 V
Underflow
Table C- 7 Voltage measuring range 1 to 5 V, 0 to 10 V
Values
Voltage measuring range
Range
dec.
hex.
1 to 5 V
0 to 10 V
32767
7FFF
>5.704 V
>11.759 V
Overflow
32511
7EFF
5.704 V
11.759 V
Overrange
27649
6C01
27648
6C00
5 V
10.0 V
Nominal range
20736
5100
4 V
7.5 V
1 1 1 V + 144.7 µV 361.7 μV
0
0
1 V
0 V
-1
FFFF
Underrange
-4864
ED00
0.296 V
-1.759 V
-32768
8000
< 0.296 V
< -1.759 V
Underflow

Table of Contents

Other manuals for Siemens Simatic S7-1500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7-1500 and is the answer not in the manual?

Siemens Simatic S7-1500 Specifications

General IconGeneral
Protection ClassIP20
Programming LanguageLAD, FBD, STL, SCL, GRAPH
Communication InterfacesPROFINET, PROFIBUS, Ethernet, OPC UA
MemoryWork memory and load memory (integrated or external memory card)
I/O ModulesDigital I/O, Analog I/O, Technology modules, Communication modules
Safety IntegratedYes (with fail-safe CPUs and modules)
RedundancyCPU redundancy possible with specific CPU types
Temperature Range0°C to 60°C (horizontal installation)
Digital InputsScalable through digital input modules
Digital OutputsScalable through digital output modules
Analog InputsScalable through analog input modules
Analog OutputsScalable through analog output modules
BackplaneIntegrated backplane for module connection
Real-time clockIntegrated real-time clock
CPU TypeVarious models available (e.g., CPU 1511-1 PN, CPU 1513-1 PN, CPU 1515-2 PN, CPU 1517-3 PN, CPU 1518-4 PN/DP)

Related product manuals