Analog value processing
C.4 Representation of output ranges
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
187
Table C- 20 Voltage output range 1 V to 5 V
Values
Voltage output range
Range
dec.
hex.
1 to 5 V
>117.589% >32511 >7EFF 5.70 V Maximum output value
117.589%
32511
7EFF
5.70 V
Overrange
27649 6C01
100%
27648
6C00
5 V
Nominal range
75%
20736
5100
4 V
0.003617%
1
1
1 V +144.7 µV
0%
0
0
1 V
-1
FFFF
1 V -144.7 µV
Underrange
-25%
-6912
E500
0 V
<-25%
<-6912
<E500
0 V
Minimum output value
C.4.2
Representation of analog values in the current output ranges
The tables below list the decimal and hexadecimal values (codes) of the possible current
output ranges.
Table C- 21 Current output range ±20 mA
Values
Current output range
Range
dec.
hex.
±20 mA
>117.589%
>32511
>7EFF
23.52 mA
Maximum output value
117.589%
32511
7EFF
23.52 mA
Overrange
27649
6C01
100%
27648
6C00
20 mA
Nominal range
75%
20736
5100
15 mA
0.003617%
1
1
723.4 mA
0%
0
0
0 mA
-1
FFFF
-723.4 mA
-75% -20736 AF00 -15 mA
-100%
-27648
9400
-20 mA
-27649
93FF
Underrange
-117.593%
-32512
8100
-23.52 mA
<-117.593%
<-32512
<8100
-23.52 mA
Minimum output value

Table of Contents

Other manuals for Siemens Simatic S7-1500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7-1500 and is the answer not in the manual?

Siemens Simatic S7-1500 Specifications

General IconGeneral
Protection ClassIP20
Programming LanguageLAD, FBD, STL, SCL, GRAPH
Communication InterfacesPROFINET, PROFIBUS, Ethernet, OPC UA
MemoryWork memory and load memory (integrated or external memory card)
I/O ModulesDigital I/O, Analog I/O, Technology modules, Communication modules
Safety IntegratedYes (with fail-safe CPUs and modules)
RedundancyCPU redundancy possible with specific CPU types
Temperature Range0°C to 60°C (horizontal installation)
Digital InputsScalable through digital input modules
Digital OutputsScalable through digital output modules
Analog InputsScalable through analog input modules
Analog OutputsScalable through analog output modules
BackplaneIntegrated backplane for module connection
Real-time clockIntegrated real-time clock
CPU TypeVarious models available (e.g., CPU 1511-1 PN, CPU 1513-1 PN, CPU 1515-2 PN, CPU 1517-3 PN, CPU 1518-4 PN/DP)

Related product manuals