Maintenance and service
5.4 Performing a firmware and project update
SIMOTION D410
186 Commissioning Manual, 02/2012
For detailed information, refer to the
SIMOTION IT Ethernet-Based HMI and Diagnostic
Functions
Diagnostics Manual.
5.4.4 Upgrade via device update tool (upgrading SIMOTION devices)
Overview
With SIMOTION V4.1 SP2 and higher, SIMOTION D Control Units and projects can be
upgraded using upgrade data that was created at an earlier point in time.
Performing an upgrade using upgrade data has the following advantages:
User-friendly creation of upgrade data via SIMOTION SCOUT with the aid of a wizard (at
the machine manufacturer's site)
SIMOTION devices can be upgraded by the machine operator without the SIMOTION
SCOUT engineering system
The machine manufacturer can conveniently send upgrade data via e-mail or post to the
machine operator
There is no need to use license keys, as licenses are retained
Retain data and unit data are retained when upgrades are performed, even across
versions
An upgrade which has been imported can be discarded again, and the previous
configuration restored
You can upgrade either a single SIMOTION device or multiple devices from one or more
SIMOTION projects.
It is possible to upgrade parts of a configuration only, e.g. Technology Packages only,
firmware only, project only, etc.
Upgrade data is created by the application engineer at the machine manufacturer's premises
using SIMOTION SCOUT. The upgrade data can then be handled flexibly depending on both
the SIMOTION device in question (SIMOTION C, D, or P) and the customer requirements:
Creating upgrade data and then copying it to a storage or upgrade medium:
CompactFlash Card
USB stick (D4x5/D4x5-2 only; not for D410)
IT DIAG file
Alternatively, the upgrade data can be created and stored in an archive on the PC, with a
view to importing it to an upgrade medium suitable for SIMOTION devices at a later point.
The process of importing the data to an upgrade medium can be performed at the
machine manufacturer's premises; alternatively, if the upgrade archive has been
transferred to the machine operator, the service engineer can do this on site.
The service engineer imports the upg
rade data on an operator-guided basis (without any
involvement by the application engineer) to the SIMOTION device(s), and upgrades the
SIMOTION devices in the process (SIMOTION SCOUT is not required on site).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D410 Series and is the answer not in the manual?

Siemens SIMOTION D410 Series Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D410 Series
CategoryController
LanguageEnglish

Related product manuals