EasyManuals Logo

Siemens SITOP PSU200M 6EP1333-3BA10 User Manual

Siemens SITOP PSU200M 6EP1333-3BA10
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
Description, device design, dimension drawing
2.5 Change-over switch
SITOP modular 1ph/2ph
14 Manual, 04.2018, C98130-A7548-A1-4-7629
2.5
Change-over switch
Figure 2-7 A/B selector switch
The two switches A and B are used to influence the output characteristic:
Switch
ON
OFF
A
influences the output
characteristic in the
load range
Parallel operation:
'Soft' characteristic curve (see, e.g.
Figure 6-10
6EP1333-3BA10 parallel operation output char-
acteristic (Page 43)) for the parallel operation of
two or more devices: The output voltage falls
with increasing output current (namely, also for
the overcurrent pulse!).
This means that for full output current the high-
est output voltage can normally no longer be
attained.
Single operation:
Delivery state
'Hard' characteristic curve (see, e.g. Figure 6-3
6EP1333-3BA10 single operation output char-
acteristic (Page 41)) for normal operation (sin-
gle operation): The output voltage is
independent of the output current.
B
influences the output
characteristic in the
overload range
Latching shutdown:
If the output current rises above the rated value
and above the current limit, the device reduces
the output voltage (see, e.g.
Figure 6-14
6EP1333-3BA10 latching shutdown output
characteristic (Page 44
)). If the output voltage
falls below 20 V, the device shuts down latch-
ing, the red LED lights up. This limit voltage of
20 V is independent of the set output voltage.
The 'Short-time overload current' feature is not
available in this operating mode. To also permit
charging of large capacitances in this operating
mode at the output, a shutdown is performed
during the first 10 s after power on or remote
switch on in conjunction with the non-latching
signaling module. During these first 10 s, the
device responds for overload as if the switch is
OFF.
Constant current:
Delivery state
If the output current rises above the rated value
and above the current limit, the device reduces
the output voltage. The yellow LED lights up if
the output voltage falls below 20 V.
Conditioned when delivered: A - OFF; B - OFF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITOP PSU200M 6EP1333-3BA10 and is the answer not in the manual?

Siemens SITOP PSU200M 6EP1333-3BA10 Specifications

General IconGeneral
BrandSiemens
ModelSITOP PSU200M 6EP1333-3BA10
CategoryPower Supply
LanguageEnglish

Related product manuals