EasyManuals Logo
Home>Smartgen>Controller>HGM6000K Series

Smartgen HGM6000K Series User Manual

Smartgen HGM6000K Series
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 11 of 34
running, controller can protect genset to stop quickly (detail procedures please
refer to No.4~9 of Auto start operation). Under Manual Test Mode , genset
with load is decided by Mains is normal or not. If mains are normal, loading
switch is never transferred; while mains are abnormal, loading switch is
transferred into gens side. Under Manual Test Mode , after genset runs well
in high speed, no matter mains is normal or not, loading switch must be
transferred into gens side.
2. HGM6010KC, Auto starts mode is active when press , and its indicator is
illuminating. Then press to start genset, it can automatic detect start
successfully and genset automatic accelerates to Hi-speed running. If there is
Hi-temperature, low oil level and voltage abnormal during diesel genset running,
controller can protect genset to stop quickly (detail procedures please refer to
No.4~9 of Auto start operation). After genset runs well in High speed, controller
will send signal of gens close.
3. Manual stop, press can shutdown the running genset (detail procedures
please refer to No.3~7 of Auto stop operation).
5 PROTECTION
5.1 WARN
Warns are non-critical alarm conditions and do not affect the operation of the
genset system; they serve to draw the operators attention to an undesirable
condition.
In the event of a warning, the module will display at the last screen of LCD.
Warn is shown as the below:
HIGH ENGINE TEMPERATURE WARN, if the module detects that the engine
coolant temperature has exceeded the high engine temperature setting level after
the Safety On timer has expired and the input of Inhibit WTH stop is activated, a
warn will occur. At the same time LCD screen icon lighten.
LOW OIL PRESSURE WARN, if the module detects that the engine oil pressure

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartgen HGM6000K Series and is the answer not in the manual?

Smartgen HGM6000K Series Specifications

General IconGeneral
BrandSmartgen
ModelHGM6000K Series
CategoryController
LanguageEnglish

Related product manuals