HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 26 of 34
7.3 DIGIT INPUT 1-5 TABLE (TABLE 3)
After the end of the delay in the safe operation,
if the signal is active, genset will immediately
alarm shutdown.
Auxiliary warn alarm digital input.
Auxiliary shutdown
alarm input
When power on, if active, genset will shut down
immediately.
During engine running, if the engine occur high
temperature shutdown, when the input is active,
the engine will first initiate cooling delay and
then stop, else will stop immediately.
The input state of genset closed.
The input state of Mains closed.
When it is active, during engine running, if the
engine appears high temperature, the engine
will only send out high temperature warning
alarm, not stop.
When it is active, during engine running, if the
engine appears low oil pressure, the engine will
only send out low oil pressure warning alarm,
not stop.
In automatic state, controller remote starts the
signal effectively when starting.
7.4 SENSOR (TABLE 4)
0 Not used
1 Defined Res. Type
2 VDO
3 SGH(Huanghe sensor)
4SGD(DongKang sensor)
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
Defined input
resistance range is
0-999.9 ohm, factory
default is SGX
0 Not used
1 Defined Res. Type
2 VDO 10Bar
3 SGH(Huanghe sensor)
4 SGD(DongKang sensor)
Defined input
resistance range is
0-999.9 ohm, factory
default is SGX