HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 6 of 34
3 SPECIFICATION
Operating Voltage
DC8.0V to 35.0V, Continuous
Power Consumption
<3W(Standby mode: ≤2W)
Alternator Input Range
3-Phase 4 Wire
2-Phase 3 Wire
Single phase 2 Wire
15VAC - 360VAC (ph-N)
15VAC - 360VAC (ph-N)
15VAC - 360VAC (ph-N)
Frequency
50Hz - 60Hz
Magnetic AC voltage
1.0V to 24V (effective value)
Magnetic AC Frequency
10,000 Hz (max)
Start Relay Output
16 Amp DC28V at supply voltage.
Fuel Relay Output
16 Amp DC28V at supply voltage.
Auxiliary Relay Output (1-4)
(1) 7Amp DC28V at supply voltage,
(2)7Amp 250VAC free voltage contact,
(3, 4)16Amp 250VAC free voltage contact.
Overall Dimensions
209mm x 153mm x 55mm
Panel cutoff
186mm x 141mm
Operating Temp. Range
Temperature: (-25~+70)ºC Humidity: (20~90)%
Storage Condition
Temperature: (-30~80)ºC
Protective Level
IP55: when waterproof rubber ring added between
controller and its panel.
IP42: when waterproof rubber ring not have
between controller and its panel.
Insulation Intensity
Object: among in input/output/power
Quote standard: IEC688-1992
Test way: AC1.5 kV / 1min 3mA leakage current
C. T. Secondary
5A (rated )
Weight
0.69kg
4 OPERATION
4.1 KEY FUNCTION
Stop/ Reset
Can stop genset under mode of Manual/Auto;
Can reset alarming under Stop;
To test panel indicators are OK or not, pressing this