HRX-OM-K003
Chapter 5 System Operation
5.3 Operation Screen HRW Series
This screen enables the setting of set values.
Table 5-10 Initial Setting Screen
Allows the selection of the band width for TEMP SP.
Allows the setting of the time from TEMP PV value
reaching BAND range to TEMP READY is displayed
and put out.
Calibrates variations in temperature between this
system and your system.
(See “Appendix 8.4 Offset Function” in Chapter 8 on
page 8-9 for details.)
Issues an alarm of “Reservoir High Temp WRN” if the
circulating fluid exceeds the set temperature.
HRW002-H, H*S:
0, 2~16LPM
0, 0.5~4.2GPM
HRW008-H, -H*S
HRW015-H, -H*S
HRW030-H, -H*S:
0, 8~50LPM
0, 2.1~13.2GPM
Issues an alarm of “Return Low Flow WRN” if the
circulating fluid does not reach the set flow rate.
Lift this alarm if the selection is “0”.
Allows the selection of the unit of flow rate.
Allows the selection of the unit of pressure.
Allows the selection of the slave address for serial
RS-485 communication.
Allows the selection of alarm signals for contact
signal. (See Appendix 8.1.3 Alarm signal selection”
on page 8-6 for details.)
Allows the selection of EVENTOutput.
(See Appendix 8.1.2 Communication specification”
on page 8-4 for details.)
Issues an alarm of “F.Water Low Temp WRN” if the
facility water falls below the set temperature.
Issues an alarm of “F.Water High Temp WRN” if the
circulating fluid exceeds the set temperature.
[Tips]
Valid during option setting with “5.3.11 Option screen“ on page 5-9.
See “Appendix 8.5 BAND/READ” in Chapter 8 on page 8-12 on
BAND/READY function (*1).
TEMP SP+OFFSET value (*2) should be in the TEMP SP setting range
defined in “Table 5-8 Setting Screen” on page 5-6.