2 Product Introduction User Manual
12
2.3.3 Derating
Derating the output power is a way to protect the inverter from overload and
potential malfunctions. Inverter’s derating function can be activated in the following
scenarios:
y
PV input overload
y
Too low grid voltage
y
Too high inner temperature
y
Power limit setting on the inverter LCD display
y
Grid frequency too high (when the Country selection is “DE” or “IT”)
PV Overload Derating
When the PV input power exceeds the defined TotalInputPowerMax, see Tab. 2-2, the
inverter will reduce the power evenly to the maximum limit and keep the output
power at nominal value.
Tab. 2-2 Maximum Input Power
Type SG10KTL SG12KTL SG15KTL SG20KTL
TotalInputPowerMax 11000W 13000W 15800W 21000W
Fig. 2-6 PV Overload Derating