User Manual 10 Operation of LCD Display Panel
71
10.10 Running Parameter Setting
10.10.1 Main Screen of Run-param
Main Screen(Press ENTER ) →Menu screen(Press j ×3) → Set-param
(Press ENTER) →Enter password(Press ENTER, Press j ) →Run-param
(Press ENTER)
On the “Run-param” screen, Press j to select one item
and Press ENTER to start this item setting.
For each item setting, Press h to move the cursor right
and Press j to set the appropriate value.
Confirm settings by Pressing ENTER.
Tab. 10-4 Specification of Running Parameters
Parameter Explanation Default Range
Standby time
The time from inverter
initialization to inverter feeding
power to grid.
20s 20…255s
Recover time
The time from the fault is cleared
to inverter feeding power to
grid.
30s
[IT:
300s]
0…900s
P-W limits Inverter active power limits. 100.0% 0...100%
Q-Var switch
Whether to start inverter reactive
power adjustment function.
[Pf]
[Pf] / [Qt] / [Off] /
[Q(P)] / [Q(U)]
PF Power factor +1.000
-1.000…-0.900 /
+0.900…+1.000
Q-Var limits Inverter reactive power limits 0.0% 0...+100% / 0…-100%
Derating
Slope*
Over-frequency power derating
slope
(
Pm/Hz
)
Only available when the
“Countries” is selected to “IT”.
83.33% 40%...100%