2) Error Processing (Binary mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type
number is returned to the computer in addition to the checksum. At time of broadcast communica-
tion of the binary mode, returning of data is not executed except for the inverter to be returned (in-
verter number 00H) and when the inverter number is not matched. This is because there will be a
risk that the returned data may be deformed.
Omissible
(3.5bytes
Blank)
“/”
(2FH)
INV-NO
1 byte
Norn
(4EH)(6EH)
DATA
2 bytes
SUM
1 byte
(3.5bytes
Blank)
Checksum area Not omissible
Norn (1 byte) : Communication error command ... This command is also used for a check when the in-
verter is tripped.
4EH (N)” is returned under normal conditions, while “6EH (n)” is returned when the in-
verter is tripped.
Data (2 bytes) : Error code (0000~0004)
0000 ... Impossible to execute (Although communication is established normally, the
command cannot be executed because it is to write data into a parameter whose
setting cannot be changed during operation (e.g., maximum frequency) or the
EEPROM is faulty.)
0001 ... Data error (The data is outside the specified range or it is composed of too many
digits.)
0002 ... Communication number error (There is no communication number that matches.)
0004 ... Checksum error (The checksum result differs.)
No code returned ...Command error, format error (parity, overrun or framing error) or the
inverter number does not match or an inverter in broadcast communi-
cation in the binary mode except for the inverter for data returning (the
inverter numbered 00H).
Examples:
2FH, 4EH, 00H, 00H, 7DH ... Impossible to execute (e.g., a change of maximum frequency data
during operation)
2FH, 4EH, 00H, 01H, 7EH ... Data setting error (The data specified falls outside the specified
range.)
2FH, 4EH, 00H, 02H, 7FH ... No communication number (There is no communication number that
matches.)
2FH, 4EH, 00H, 04H, 81H ... Checksum error (The checksum result differs.)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals