E6581913
67
9.Parameter data
Explanation of parameters for VF-S15 series is described here. For communication purposes, see
the parameter list on inverter's instruction manual
regarding the communication number, adjustment
range and so forth.
Referring to the parameter list
<Example of excerpts from the inverter’s instruction manual>
Title
Commu-
nication
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Ref-
erenc
e
auh - History function - - -
4.3
5.1
aua Apprication easy
setting
- - 0
auf - Guidance function - - 0
4.3
5.2
aul 0094 Overload character-
istic selection
0:-
1:Constant torque charac-
teristic (150%-60s)
2:Variable torque charac-
teristic (120%-60s)
1/1
0
3.5
5.3
6.14
au1 0000 Automatic accelera-
tion/deceration
0:Disabled(manual setting)
1:Automatic
2:Automatic(only at accel-
eration)
1/1
0
5.4
acc
0009 Acceleration time 1 0.0~3600 sec.
0.1/0.1 10.0
5.4
:
- The summary of parameter list relating to the communication is as follows.
(1) “Title” means the display on the inverter panel.
(2) “Communication number” is affixed to each parameter that is necessary for designating the parameter for com-
munication.
(3) "Adjustment range" means a data range adjustable for a parameter, and the data cannot be written outside the
range. The data have been expressed in the decimal notation. For writing the data through the communication
function, take the minimum setting unit into consideration, and use hexadecimal system.
(4) "Minimum setup unit" is the unit of a single data (when the minimum setting unit is "-", 1 is equal to 1).
For example, the "minimum setting unit" of acceleration time (
acc) is 0.1, and 1 is equal to 0.1s. For setting a
data to 10 seconds, transmit 64h [10
÷0.1=100d=64h] by communication.
If 0999 is equal to 2, the acceleration/deceleration time parameters
acc, dec, f500, f501, f510,
f511 can be set in units of 0.1 sec. If 0999 is equal to 1, these parameters can be set in units of 0.01 sec.
Acceleration/deceleration setting time unit (0999)
Communication No. Function name Unit Adjustment range
0999 Acceleration/deceleration time unit
-
1: 0.01 sec. (0.01-360.00)
2: 0.1 sec. (0.1-3600.0)
Note: Don’t write the communication number of 0999. The acceleration/deceleration time unit is set by f519.
(5) When data is a negative number, it treats as an one's complement expression (ex. FFFFH is equal to ‘-1’).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals