E6581913
24
5. Modbus RTU protocol
The Modbus RTU protocol of VF-S15 supports only part of the Modbus RTU protocol. All data will
be binary codes.
Parameter Setting
Protocol selection (f829)
Select “Modbus RTU (f829 = 1) in the communication selection parameters. “TOSHIBA”
(f829=0) is set for communication protocol selection in initial shipment setting. (See “3. Com-
munication protocol”.)
Inverter number (f802)
Inverter numbers. 0 to 247 can be specified in the Modbus RTU. “0” is allocated to broadcast
communication (no return). Set between 1 and 247.
<Related Parameter: Change and set as necessary>
f800 : Baud rate
f801 : Parity
Data Exchange with Inverters
The inverters are always ready to receive messages and perform slave operation in response to
computer requests.
A transmission error will result if the transmission format does not match. The inverters will not
respond if a framing error, parity error, CRC error or an inverter number mismatch occurs. If no re-
sponse is received, the computer side recognizes that a communication error has occurred.
Transmit data again.
(1) In case spacing for more than 3.5 bytes are provided before characters, all data immediately
preceding it will be aborted. (See “3.1. About the handling of received frames”.)
(2) Communication w
ill be effective only when inverter
numbers match or the communication mode
is 0 (Broadcast communication). If there is no inverter number that matches or 0 (broadcast
communication) is specified, no response is returned by any inverter.
(3) If no communication take place within the time specified using the timer function, the computer
will assume that a communication error has occurred and trip the inverter. The timer function is
disabled when the inverter is turned on or initialized. For details, see “7.3. Communication
time-out detection”.
(4) On executing the command received,
the inverter returns data to the computer. Fo
r the re-
sponse time, see Appendix 2, “Response time”.
Caution:
Communication is not possible for about one second after the power is supplied to the inverter until
the initial setting is completed. If the control power is shut down due to an instantaneous voltage
drop, communication is temporarily interrupted.