E6581913
33
5.1.5. Block Write command (10H)
Select data, which is desired to be written in block communications, in Block Communication Write
Data 1 and 2 Parameters (f870, f871). This parameter becomes effective when the system
is reset, such as when power is turned off. When the setting is completed, turn off and then on the
power.
No. Block write data For data details, see:
0 No selection -
1 Communication command 1 (FA00)
2 Communication command 2 (FA20)
3 Frequency command value (FA01)
4 Output data on the terminal board (FA50)
5 FM analog output (FA51)
6 Motor speed command (FA13)
“8.1. Command by communication”
* When “No selection” is specified in the parameters, no data will be written even though write data
is specified.
Computer → Inverter *The text size is 13 bytes fixed.
Communication
No.
number of word Write Data 1 Write Data 2 CRC16
Inverter
No.
Command
high low high low
number
of byte
high low high low low high
10 18 70 00 02 04
1) Inverter No. (1 byte) : ---
2) Command (1 byte) : Set the block write command (10H fixed).
3) Communication No. (2 bytes) : Set in the order of high to low numbers (1870H fixed).
4) Number of word (2 bytes) : 0002H (fixed).
5) Number of byte (1 bytes) : 04H (fixed).
6) Write data 1(2 bytes) : Set in the order of high to low write data 1.
The data is written to the specified parameter selected by f870.
6) Write data 2(2 bytes) : Set in the order of high to low write data 2.
The data is written to the specified parameter selected by f871.
8) CRC16 (2 bytes) : ---
Inverter → Computer (Normal return) *The text size is 8 bytes fixed.
Communication
No.
number of word CRC16
Inverter
No.
Command
high low high low low high
10 18 70 00 02
1) Inverter No. (1 byte) : ---
2) Command (1 byte) : 10H (fixed).
3) Communication No. (2 bytes) : 1870H (fixed).
4) Number of word (2 bytes) : 0002H (fixed).
5) CRC16 (2 bytes) : ---