E6581913
20
4.3.
Transmission errors
Table of error codes
Error name Description Error code
Impossible to exe-
cute
The command is impossible to execute, though communication was
established normally.
1 Writing data into a parameter whose setting cannot be changed
during operation (e.g., maximum frequency)
*1
2 Writing data into a parameter while “init” is in progress
3 f700 (Parameter protection selection) is 2: Writing prohibited
(1+RS485 communication), 4: Reading prohibited (3+RS485
communication)
4 If f738(Password setting) was set to data, f738 can not set
to data
0000
Data error Invalid data is specified. 0001
Communication
number error
There is no communication number that matches. 0002
Command error The command specified does not exist. 0003 (ASCII mode)
No code returned (Binary
mode)
Checksum error The checksum does not match. 0004
Format error The data transmission format does not match.
1 One-digit inverter number (ASCII mode)
2 The CR code is found in the designated position. (ASCII mode)
Ex.: Communication number of 4 digits or less. In the case of
(R11) CR, 11) CR is recognized as a communication number
and the CR code is not recognized, with the result that a
format error occurs.
3 A code other then the stop code (“)”) is entered in the stop code
position.
No code returned
Receiving error A parity, overrun or framing error has occurred.
*2
No code returned
*1: For parameters whose settings cannot changed during operation, see the inverter’s instruction
manual.
*2: Parity error : The parity does not match.
Overrun error : A new data item is entered while the data is being read.
Framing error : The stop bit is placed in the wrong position.
* For the errors with “no code returned” in the above table, no error code is returned to avoid a
data crash.
If no response is received, the computer side recognizes that a communication error has oc-
curred. Retry after a lapse of some time.
* If the inverter number does not match, no processing will be carried out and no data will be re-
turned, though it is not regarded as an error.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals